Boiler Water Analysis — Don’t Just Check the pH

Boiler water analysis is one of the simplest ways to prevent expensive boiler problems.

A proper analysis should normally include:

🔹 pH — indicates the alkalinity condition and helps control corrosion.
🔹 Phosphate (PO₄) — confirms that the phosphate treatment is working and helps prevent scale formation.
🔹 Chloride (Cl⁻) — a key indicator of seawater contamination. A sudden increase is a warning sign.
🔹 Sulphite / Oxygen Scavenger — confirms that dissolved oxygen is being chemically controlled.
🔹 Alkalinity (P/M) — important for controlling caustic conditions and preventing corrosion or caustic attack.
🔹 Conductivity / TDS — shows the concentration of dissolved salts and helps determine the need for blowdown.

⚠️ The important part

Do not correct the chemistry blindly.

If chloride and conductivity suddenly rise, adding more chemicals is not the solution.

👉 First look for the cause:
condenser leakage, contaminated make-up water, faulty feedwater treatment, or insufficient blowdown.

And remember:

Good boiler water is not the water with the highest chemical concentration.
It is water maintained within the correct limits for that particular boiler and treatment programme.